- Phase
- Single Phase
- Form Factor
- Rackmount, Tower
- UPS Topology
- Online Double Conversion
- Energy Saving Technology
- ECO Mode Efficiency > 95%
- Active PFC Compatibility
- Yes
- Generator Compatibility
- Yes
- Nominal Input Voltage ( Vac )
- 230 ± 10%
- Input Voltage Range ( Vac )
- 160 ~ 300
- Adjustable Voltage Range ( Vac )
- 0~30% Load for 80 ~ 300 Vac, 0~60% Load for 120 ~ 300 Vac, 0~80% Load for 140 ~ 300 Vac, 0~100% Load for 160 ~ 300 Vac
- Input Frequency ( Hz )
- 50 ± 10, 60 ± 10
- Input Frequency Detection
- Auto-sensing
- Rated Input Current ( A )
- 4.5
- Input Power Factor
- 0.99
- Input Connector Type
- IEC C14
- Detachable Power Cord Plug Type
- Schuko x 1
- Power Cord Length (m.)
- 1.5
- Capacity (VA)
- 1000
- Capacity (Watts)
- 900
- On Battery Waveform
- Pure Sine Wave
- On Battery Voltage(s) ( Vac )
- 208 ± 1 %, 220 ± 1 %, 230 ± 1 %, 240 ± 1 %,
- Output Voltage Setting
- Configurable
- On Battery Frequency ( Hz )
- 50 ± 0.5%, 60 ± 0.5%
- Output Frequency Setting
- Configurable
- Power Factor
- 0.9
- ECO Mode Voltage Tolerance
- ± 15 %
- Overload Protection
- Internal Current Limiting, Circuit Breaker, Fuse
- Overload Protection (Line Mode)
- 110~120% Load for 1 min, >120% Load Immediately
- Overload Protection (Battery Mode)
- 110~120% Load for 10 sec, >120% Load Immediately
- Overload Protection (Bypass Mode)
- >130% Load Immediately
- Crest Factor
- 3 : 1
- Harmonic Distortion (Linear Load)
- THD<3%
- Harmonic Distortion (Non-linear Load)
- THD<5%
- Internal Bypass
- Automatic Bypass, Manual Bypass
- Outlet(s) - Total
- 8
- Outlet Type
- IEC C13 x 8
- Outlet(s) - Battery & Surge Protected
- 8
- Outlet(s) - Critical Load (CL)
- 4
- Outlet(s) - Non-critical Load (NCL)
- 4
- Typical Transfer Time ( ms )
- 0
- Runtime at Half Load ( min )
- 13.9
- Runtime at Full Load ( min )
- 4.6
- Typical Recharge Time ( Hours )
- 4
- Maximum Charging Current ( A )
- 1.5
- Start On Battery
- Yes
- Smart Battery Management (SBM)
- Yes
- User-replaceable
- Yes - Qualified Personnel Only
- Hot-swappable
- Yes - Qualified Personnel Only
- Battery Type
- Sealed Lead-acid
- Replacement Battery Pack (RBP)
- RBP0156
- Replacement Battery Pack (RBP) Quantity ( pcs )
- 1
- Battery Quantity (Each RBP) ( pcs )
- 2
- Battery Voltage (Each RBP) ( V )
- 24
- Compatible Extended Battery Module (EBM)
- BPSE24V40ART2U
- Extended Battery Module Auto-detection
- Yes
- Max. EBM Quantity ( pcs )
- 3
- Surge Suppression ( Joules )
- 363
- EMI/RFI Filtration
- Yes
- Phone/Network Protection RJ11/RJ45 (Combo)
- 1-in, 1-out
- LCD Panel
- Yes
- LCD Types
- Color LCD
- LCD Orientation
- Rotatable LCD – Manual
- LCD Information Display
- Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log
- LCD Setting & Control
- Mode Setting, Alarm Setting, Input & Output, Battery Setting
- HID Compliant USB Port(s)
- 1
- Dry Contact (with Relay)
- Yes
- Emergency Power Off (EPO) Port
- Yes
- Audible Alarms
- Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery
- Management Cable ( pcs )
- Power Cord x2, USB Cable x1
- Power Management Software
- PowerPanel Business (Recommended)
- SNMP/HTTP Remote Monitoring
- Yes - with optional RMCARD205
- Enclosure Construction
- Metal
- Color
- Black
- Rackmount Rail
- Yes
- Rackmount Ears
- Yes
- Dimensions (WxHxD) (mm.)
- 438 x 88 x 430
- Weight (kg.)
- 13.5
- Installed Rack Height ( U )
- 2
- Operating Temperature (°C)
- 0 ~ 40
- Operating Relative Humidity (Non-condensing) ( % )
- 5 ~ 95
- Operating Elevation ( meters )
- 0-1,500 meters
- Storage Temperature (°C)
- -20 ~ 50
- Storage Relative Humidity (Non-condensing) ( % )
- 10 ~ 90
- Storage Elevation ( meters )
- 0-1,500 meters
- Online Thermal Dissipation ( BTU/hr )
- 380
- Variable Speed Fans
- 20 steps automatically
- Audible Noise at 1.5M from Surface of Unit ( dBA )
- 45
- Certifications
- CE, EAC, TISI
- RoHS
- Yes